SCHNEIDER LC1D50Af7

SCHNEIDER LC1D50Af7 Contactores TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 50 A – 110 V AC 50/60 Hz coil

Categoría:

Especificaciones:

 

gama de producto
TeSys D
gama
TeSys
nombre del producto
TeSys D
tipo de producto o componente
Conector
nombre corto del dispositivo
LC1D
aplicación del contactor
Control del motor
Carga resistiva
categoría de empleo
AC-1
AC-3
AC-4
número de polos
3P
composición de los polos de contacto
3 NA
[Ue] tensión asignada de empleo
<= 300 V DC for power circuit
<= 690 V AC 25…400 Hz for power circuit
[Ie] corriente asignada de empleo
50 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
80 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
potencia del motor en kW
22 kW at 380…400 V AC 50/60 Hz AC-3
25 kW at 415 V AC 50/60 Hz AC-3
30 kW at 440 V AC 50/60 Hz AC-3
30 kW at 500 V AC 50/60 Hz AC-3
33 kW at 660…690 V AC 50/60 Hz AC-3
15 kW at 220…230 V AC 50/60 Hz AC-3
11 kW at 400 V AC 50/60 Hz AC-4
potencia del motor en HP
3 hp at 115 V AC 50/60 Hz for 1 phase motors
7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
15 hp at 200/208 V AC 50/60 Hz for 3 phases motors
15 hp at 230/240 V AC 50/60 Hz for 3 phases motors
40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
40 hp at 575/600 V AC 50/60 Hz for 3 phases motors
tipo de circuito de control
AC 50/60 Hz
[Uc] tensión del circuito de control
110 V AC 50/60 Hz
composición de los contactos auxiliares
1 NA + 1 NC
[Uimp] Tensión asignada de resistencia a los choques
Conforming to IEC 60947
categoría de sobretensión
III
[Ith] corriente térmica convencional
80 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit
Irms poder de conexión nominal
900 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
poder asignado de corte
900 A at 440 V for power circuit conforming to IEC 60947
[Icw] Corriente temporal admisible
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
400 A <= 40 °C 10 s power circuit
810 A <= 40 °C 1 s power circuit
84 A <= 40 °C 10 min power circuit
208 A <= 40 °C 1 min power circuit
fusible asociado
100 A gG en <= 690 V coordinación tipo 1 para circuito de alimentación
100 A gG en <= 690 V coordinación tipo 2 para circuito de alimentación
10 A gG para circuito de señalización acorde a IEC 60947-5-1
impedancia media
1.5 mOhm en 50 Hz – Ith 80 A para circuito de alimentación
[Ui] tensión asignada de aislamiento
600 V for power circuit certifications CSA
600 V for power circuit certifications UL
690 V for power circuit conforming to IEC 60947-4-1
690 V for signalling circuit conforming to IEC 60947-1
600 V for signalling circuit certifications CSA
600 V for signalling circuit certifications UL
durabilidad eléctrica
1.45 Mcycles 50 A AC-3 at Ue <= 440 V
1.1 Mcycles 80 A AC-1 at Ue <= 440 V
potencia disipada por polo
3.7 W AC-3
9.6 W AC-1
cubierta protectora
Con
tipo de montaje
Placa
Carril
normas
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
certificaciones de producto
BV
CCC
CSA
DNV
GL
GOST
LROS (Lloyds register of shipping)
RINA
UL
conexiones – terminales
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² – cable stiffness: flexible – with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: flexible – without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm² – cable stiffness: flexible – without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: flexible – with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: solid – without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm² – cable stiffness: solid – without cable end
Power circuit : screw connection 2 cable(s) 1…25 mm² – cable stiffness: flexible – with cable end
Power circuit : screw connection 2 cable(s) 1…25 mm² – cable stiffness: solid – without cable end
Power circuit : screw connection 2 cable(s) 1…25 mm² – cable stiffness: flexible – without cable end
Power circuit : screw connection 1 cable(s) 1…35 mm² – cable stiffness: solid – without cable end
Power circuit : screw connection 1 cable(s) 1…35 mm² – cable stiffness: flexible – without cable end
Power circuit : screw connection 1 cable(s) 1…35 mm² – cable stiffness: flexible – with cable end
par de apriete
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
Power circuit: 8 N.m – on EverLink BTR screw connectors – cable 25…35 mm² hexagonal 4 mm
Power circuit : 5 N.m – on EverLink BTR screw connectors – cable 1…25 mm² hexagonal 4 mm
duración de maniobra
12…26 ms closing
4…19 ms opening
nivel de fiabilidad de seguridad
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
endurancia mecánica
6 Mcycles
rango de operación
3600 cyc/h at <= 60 °C
característica de la bobina
Sin filtro antiparasitario de serie
límites de tensión del circuito de control
0.3…0.6 Uc drop-out at 60 °C, AC 50/60 Hz
0.8…1.1 Uc operational at 60 °C, AC 50 Hz
0.85…1.1 Uc operational at 60 °C, AC 60 Hz
Consumo a la llamada en VA
140 VA at 20 °C (cos ϕ 0.75) 60 Hz
160 VA at 20 °C (cos ϕ 0.75) 50 Hz
consumo de mantenimiento en VA
13 VA at 20 °C (cos ϕ 0.3) 60 Hz
15 VA at 20 °C (cos ϕ 0.3) 50 Hz
disipación de calor
4…5 W at 50/60 Hz
tipo de contactos auxiliares
Tipo unido mecánicamente (1 NA + 1 NC) acorde a IEC 60947-5-1
Tipo contacto espejo (1 NC) acorde a IEC 60947-4-1
frecuencia del circuito de señalización
25…400 Hz
corriente mínima de conmutación
5 mA for signalling circuit
tensión mínima de conmutación
17 V for signalling circuit
tiempo de no superposición
1.5 ms on de-energisation (between NC and NO contact)
1.5 ms on energisation (between NC and NO contact)
resistencia de aislamiento
> 10 MOhm for signalling circuit
compatibilidad de contacto
M2
código de compatibilidad
LC1D
rango de potencia
7…11 kW 200…240 V 3 phases
15…25 kW 200…240 V 3 phases
15…25 kW 380…440 V 3 phases
30…50 kW 380…440 V 3 phases
30…50 kW 480…500 V 3 phases
tipo de arranque motor
Contactor directo
tension de la bobina del contactor
110 V AC standard
grado de protección IP
IP20 front face conforming to IEC 60529
tratamiento de protección
TH conforming to IEC 60068-2-30
grado de contaminación
3
temperatura ambiente de funcionamiento
-5…60 °C
temperatura ambiente de almacenamiento
-60…80 °C
temperatura ambiente admisible alrededor del dispositivo
-40…70 °C at Uc
altitud máxima de funcionamiento
3000 m without derating in temperature
resistencia al fuego
850 °C conforming to IEC 60695-2-1
resistencia a las llamas
V1 conforming to UL 94
resistencia mecánica
Vibrations contactor open 2 Gn, 5…300 Hz
Vibrations contactor closed 4 Gn, 5…300 Hz
Shocks contactor open 10 Gn for 11 ms
Shocks contactor closed 15 Gn for 11 ms
altura
122 mm
anchura
55 mm
profundidad
120 mm
peso del producto
0.855 kg