Medición de resistencia de tierra de 3 y 2 polos (0.01Ω-2000Ω).
• Diseño a prueba de agua (IP67).
• Rotary Switch hace que la interfaz de usuario sea muy intuitiva.
• Gran pantalla LCD con luz de fondo.
• Led para monitorear la resistencia a picos de tierra auxiliar correcta / no correcta.
• Medición del voltaje de la tierra (AC / DC 0-300V).
• CAT IV 100V.
Earth resistance measurement |
20Ω | 200Ω | 2000Ω | ||||
---|---|---|---|---|---|---|---|
Measuring range | 0.00 – 2000 Ω | ||||||
Display range | 0.00 – 20.99 Ω | 0.0 – 209.9 Ω | 0 – 2099 Ω | ||||
Accuracy*1 | ±1.5%rdg±0.08 Ω*2 | ±1.5%rdg±4dgt | |||||
Auxiliary earth resistance*3 | <10kΩ | <50kΩ | <100kΩ | ||||
Comparator reference value | 10Ω | 100Ω | 500Ω | ||||
Earth voltage measurement | |||||||
Measuring range | 0 – 300 V AC (45 – 65Hz) | ±0 – ±300 V DC | |||||
Display range | 0.0 – 314.9 V | 0.0 – ±314.9 V | |||||
Accuracy | ±1%rdg±4dgt | ||||||
Overload protection | Earth resistance : 360V AC (10 seconds) | ||||||
Earth voltage : 360V AC (10 seconds) | |||||||
Applicable Standards | IEC 61010-1, CAT IV 100 V /CAT III 150 V /CAT II 300 V Pollution degree 3 | ||||||
IEC 61010-2-030,IEC 61010-031, IEC 61557-1, -5 | |||||||
IEC 60529 IP67, IEC 61326-1, -2-2, EN50581(RoHS) | |||||||
Power source | LR6(AA)(1.5V) × 6 | ||||||
Dimensions | 121(L) × 188(W) × 59(H) mm (including case lid) | ||||||
Weight | Approx. 690g (including batteries and case lid) | ||||||
Accessories for 4105DL |
7127B(Simplified measurement probe) | ||||||
8041(Auxiliary earth spikes[2 spikes/1set]) | |||||||
9121(Shoulder strap) | |||||||
7267(Cable reel for Earth resistance tester (red)) | |||||||
7268(Cable reel for Earth resistance tester (yellow)) | |||||||
7271(Earth resistance test leads) | |||||||
9190(Carrying case) | |||||||
LR6(AA) × 6, Instruction manual | |||||||
Accessories for 4105DL-H |
7127B(Simplified measurement probe) | ||||||
8041(Auxiliary earth spikes[2 spikes/1set]) | |||||||
9121(Shoulder strap) | |||||||
7266(Earth resistance test leads[red-20m, yellow-10m, green-5m/1set]) | |||||||
9191(Hard case) | |||||||
LR6(AA) × 6, Instruction manual | |||||||
Optional | 7272(Precision measurement Cord set) | ||||||
8259(Adapter for measurement terminal) |
*1 For precision measurement, auxiliary earth resistance should be 100 Ω ±5% or less.
*2 At simplified measurement add ±0.10 Ω to the specified accuracy.
*3 Accuracy within the auxiliary earth resistance: ±5% rdg ±10 dgt.